+44 (0) 20 8405 6789
or email: sales@etscablecomponents.com
12 kV MONOi3 W – 12MONOi3.95W
HEAT-SHRINK MV INDOOR TERMINATION FOR THREE CORE POLYMERIC CABLES WITH STA OR SWA ARMOR
Up to 20,8/36 (42) kV
APPLICATION
The ‘’MONOi3 W” indoor terminations are designed for armored three core polymeric cables with Cu wire or tape screen.
TECHNICAL FEATURES
The ‘’MONOi3 W’’ indoor terminations are designed for max system voltages
of 42 kV, for compact switchgears as well as for installations where space is limited.
Easy, quick to install, reducing installation time and errors.
The kit consists of a stress control mastic pad, a co extruded dual wall tube and red anti-tracking sealing mastic.
Red anti-tracking break-out and red anti-tracking tubes “GT2” with adjustable length “D” are included in the kit.
The design accommodates various conductor lugs.
MC types are supplied with “GPH” mechanical conductor lugs
Right angle or straight heat-shrinkable boots are available on request.
Um kV | Section range (mm²) | DOI insulation (mm) | DOE Outer Sheath | L min (mm) | 12 kV | 25-95 | 12-20 | 38-56 | 500 |