• Skip to primary navigation
  • Skip to main content
  • Skip to primary sidebar
+44 (0) 20 8405 6789
sales@etscablecomponents.com
  • Products
    • Cable Glands Adaptors & Reducers
    • Cable Cleats & Cable Ties
    • Electrical Cable Lugs & Connectors
    • LV Cable Jointing and Heat Shrink
    • Medium Voltage Terminations & Joints
    • Screened Separable Connectors
    • Pfisterer CONNEX
    • Earthing and Lightning Protection
    • nVent ERICO Cadweld Exothermic Welding
    • ERICO Signal Reference Grid Products
    • Cable duct sealing system
    • Crimping & Cutting Tools and Tool Hire
    • Corrosion Protection Products
    • Cable Markers & Insulation Products
    • Flexible Conduit
    • Powersafe High Current Connectors
    • Street Lighting Fusegear & Fuses
    • Plastic Electrical Enclosure Boxes
    • Cable Tray Unistrut & Cable Ladder Systems
  • Manufacturer
    • 3M
    • Birkett
    • Cembre
    • CMP
    • DENSO
    • Derancourt
    • Ellis Patents
    • Elastimold
    • nVent ERICO
    • Euromold
    • FiloForm
    • Flexicon
    • Hawke
    • HellermannTyton
    • Lucy Zodion
    • Nexans
    • Pfisterer
    • Powersafe
    • Prysmian
    • Raychem RPG
    • Raxton
    • Ripley
    • Sonel
    • TE Connectivity
  • Sectors
    • Data Centres
    • Hazardous Areas
    • LUL – London Underground
    • PV Solar Farms
    • Surface Rail
    • Utilities
    • Wind Farms
    • Waste to Energy
  • Services
    • Training and Assessments
    • Tool hire
    • Tool Repair Calibration
  • Contact
    • Cookie Policy
  • Login
  • Your quote 0
Call
0
Quote
  • Your quote
  • Login
  • Register
  • Products
    • Cable Glands Adaptors & Reducers
    • Cable Cleats & Cable Ties
    • Electrical Cable Lugs & Connectors
    • LV Cable Jointing and Heat Shrink
    • Medium Voltage Terminations & Joints
    • Screened Separable Connectors
    • Pfisterer CONNEX
    • Earthing and Lightning Protection
    • nVent ERICO Cadweld Exothermic Welding
    • ERICO Signal Reference Grid Products
    • Cable duct sealing system
    • Crimping & Cutting Tools and Tool Hire
    • Corrosion Protection Products
    • Cable Markers & Insulation Products
    • Flexible Conduit
    • Powersafe High Current Connectors
    • Street Lighting Fusegear & Fuses
    • Plastic Electrical Enclosure Boxes
    • Cable Tray Unistrut & Cable Ladder Systems
  • Manufacturer
    • 3M
    • Birkett
    • Cembre
    • CMP
    • DENSO
    • Derancourt
    • Ellis Patents
    • Elastimold
    • nVent ERICO
    • Euromold
    • FiloForm
    • Flexicon
    • Hawke
    • HellermannTyton
    • Lucy Zodion
    • Nexans
    • Pfisterer
    • Powersafe
    • Prysmian
    • Raychem RPG
    • Raxton
    • Ripley
    • Sonel
    • TE Connectivity
  • Sectors
    • Data Centres
    • Hazardous Areas
    • LUL – London Underground
    • PV Solar Farms
    • Surface Rail
    • Utilities
    • Wind Farms
    • Waste to Energy
  • Services
    • Training and Assessments
    • Tool hire
    • Tool Repair Calibration
  • Contact
    • Cookie Policy
  • Products
    • Cable Glands Adaptors & Reducers
    • Cable Cleats & Cable Ties
    • Electrical Cable Lugs & Connectors
    • LV Cable Jointing and Heat Shrink
    • Medium Voltage Terminations & Joints
    • Screened Separable Connectors
    • Pfisterer CONNEX
    • Earthing and Lightning Protection
    • nVent ERICO Cadweld Exothermic Welding
    • ERICO Signal Reference Grid Products
    • Cable duct sealing system
    • Crimping & Cutting Tools and Tool Hire
    • Corrosion Protection Products
    • Cable Markers & Insulation Products
    • Flexible Conduit
    • Powersafe High Current Connectors
    • Street Lighting Fusegear & Fuses
    • Plastic Electrical Enclosure Boxes
    • Cable Tray Unistrut & Cable Ladder Systems
  • Manufacturer
    • 3M
    • Birkett
    • Cembre
    • CMP
    • DENSO
    • Derancourt
    • Ellis Patents
    • Elastimold
    • nVent ERICO
    • Euromold
    • FiloForm
    • Flexicon
    • Hawke
    • HellermannTyton
    • Lucy Zodion
    • Nexans
    • Pfisterer
    • Powersafe
    • Prysmian
    • Raychem RPG
    • Raxton
    • Ripley
    • Sonel
    • TE Connectivity
  • Sectors
    • Data Centres
    • Hazardous Areas
    • LUL – London Underground
    • PV Solar Farms
    • Surface Rail
    • Utilities
    • Wind Farms
    • Waste to Energy
  • Services
    • Training and Assessments
    • Tool hire
    • Tool Repair Calibration
  • Contact
    • Cookie Policy
You are here: HomeArchives for admin

admin

Using the VRQ+ Vulcan Quadrofoil Cleat In A Single Phase

June 26, 2013 by admin

The VRQ+ Vulcan Quadrofoil cable cleat is principally designed to restrain and support single-core cables routed in dedicated TPN (three-phase & neutral) circuits.

The VRQ+ range can also, hypothetically, be used to restrain four, single-core cables running in parallel and forming one single phase. BUT, sufficient air-clearances around each phase need to be maintained due to heat-cycling.

Air-clearance between phase formations

The BS7671 standard is not completely clear on the necessary air-clearance required, but it is generally accepted that the minimum clearance required is the diameter of at least one cable. It is important to consider that four single-core cables in parallel would equate to one “cable diameter”, we would advise that at least the overall width of the four single-core cable formation be used.

For example, if you had four cables each of 50mm diameter, their Quad formation would be 100mm width. Therefore, there should be at least 100mm free air-space between phase formations.

Cleating in limited space

Due to space limitations, this sort of installation may not be feasible on site. If this is the case we would advise that the cables are run in three-phase sets within VRT+ trefoil cleats, with the neutrals stacked within our single way aluminium cleats. Please contact our Sales Team for more information.

If you found this article helpful or interesting, please share it!

Filed Under: Products

The Electric Event 2013

June 20, 2013 by admin

All eyes are on the ICC Birmingham this week as the annual Electrical Contractors’ Associastion (ECA) conference takes place between 20th – 22nd June.

The Electric Event is a must for businesses within the building services or electrical contracting industry. The conference itself is focusing on understanding and managing change, keeping on top of new legislation and remaining profitable in a recession. Delivering fresh thinking, valuable insights and new opportunities, the event is full of key speakers, workshops and a chance to meet a number of suppliers at their exhibition stands.

Conference Speakers

There is a whole host of key industry speakers hosting talks on day 1 and 3 of the event, including Phil Fagg the ECA President, Steve Bratt the ECA CEO and David Philp of the Building Information Modelling (BIM) task group to name a few.

Workshop Streams

Day 2 features the ‘Meet the Suppliers’ exhibition as well as numerous workshops. The Technology Live workshops are an ideal opportunity for electrical contractors, consultants, designers and specifiers to hear directly from leading industry manufacturers about their latest products and innovations.

We’re particularly looking forward to ”Fire performance cables: Applications, features and which specifications to use to get it right” by Martyn Corbishley of Prysmian Cables.

If you’re attending let us know how you found the event in the comments below.

Filed Under: Industry

Hydraulic Crimping and Cutting Tool Maintenance

June 14, 2013 by admin

Whether you are buying or hiring a hydraulic cable crimper or cutter, following these guidelines helps prevent more than just tool failure and time lost on site.

An example of this is incorrect crimping, which can lead to a number of issues with lug failure. If the tool is unable to properly crimp the lug to the cable, then the air pockets within the core can cause an increase in resistance leading to overheating and potentially a fire. The following images show an installation where an electrical lug was installed with an uncalibrated tool with inadequate pressure. This led to the fire bridge being called, the building being evacuated and losing 2 hours of operating time.

Crimp lug failure Incorrect crimp

Typically, hydraulic tools are naturally robust given nature of the tasks they are designed for, however, we always recommend you ensure your tools are in date in terms of calibration and the on-site team is reminded about the importance of pre-use checks and tests, as well as demonstrating the results if a crimp is not undertaken carefully.

Our hydraulic tool maintenance guide gives you a few simple steps that can help avoid tool failure, hydraulic oil leakage and head jamming.

General Maintenance

When you hire or purchase a tool you should also check its condition as soon as you receive it, making sure there are no defects that could impact performance. Usually, tools distributed from reputable companies are calibrated, tested and guaranteed before delivery. However, checking yourself should be the final line of defence.

All tools we supply come with full operation instructions, these instructions should be followed as not only do they help achieve the best cut or crimp, they also keep the tool within safe operating conditions. Keeping to these guidelines will ensure the tool works to its best capacity as well as allowing it to maintain this performance throughout its operational life.

How often should I calibrate my crimper/cutter?

Whenever you hire or first purchase a hydraulic Cembre cutting or crimping tool from ETS, we fully test and calibrate your tool before delivery, supplying a calibration certificate with the tool. For short to medium term hires it is unlikely that the tool will need calibration while on its hire period. However, with long term rental and purchasing a tool, knowing when to calibrate your tool is important.

It is recommended that you get your hydraulic tool calibrated every 12 months. Calibration will test the pressure of your tool using a manometer. The pressure measurement test will make sure the tool meets the recommended level of pressure to enable the correct crimping or cutting operation. If the tool does not meet the required minimum pressure, it needs to be sent to the manufacturer for repair. We can carry out full calibration services for Cembre tools, please contact us for more information.

How to correctly store a hydraulic tool

All our Cembre hydraulic tools are supplied with protective storage cases, with enough room to store the tool or head and a number of die sets. These cases help keep the tool safe from damage on-site as well as providing an easy way to transport the tool to, from and around a project.

We recommend keeping the tool within the heavy-duty protective case while not in use as not only does it protect the tool from damage but also keeps harmful dirt and greases away from clogging the mechanisms.

Lifespan of a well maintained tool

A faulty tool is not just costly if you need to purchase a replacement, it can also be time consuming to organise collection and delivery of replacement tooling. Leading to increased time on site and a reduction in productivity, which could have a ripple effect down the line if essential work is reliant on the crimping or cutting of cables.

We offer a full 12 month warranty with all Cembre hydraulic tools we hire and sell. Although following these tool care and maintenance guidelines will enable your tool to work far beyond this period, reduce tool failure downtime and extend its operational life-span to its maximum potential.

If you found this article helpful or interesting, please share it!

Filed Under: Knowledge, Products

ETS Help Supply The Shard

June 10, 2013 by admin

The Shard, also known as the Shard of Glass is a brand new skyscraper next to London Bridge. Construction work began in March 2009 and was completed in March 2012, opening to the public in February this year. Standing at an impressive 309.6 meters (1,016 ft), the Shard is the tallest building in Western Europe.

ETS were proud to help supply this iconic building and we take a look back at what products we supplied for the project.

We originally submitted samples and data sheets for approval in 2008. Working with both the main contractor and consultant to provide suitable products that would compliment the high quality engineering standards of the project design, as well as stand the test of time.

On this basis, the products short listed for approval were provided by CMP, Ellis Patents and Cembre. It was felt each of these manufacturers provided stringent enough product testing to ensure that cabling contractors would be able to deliver the highest quality installation.

The Shard was also awarded ‘Major Building Project of the Year’ (Over £50m) at the British Construction Industry (BCI) awards 2013.

 

Filed Under: Projects

Preview: Medium Voltage Cable Accessories – A Book By Derek Goulsbra Part 2

May 30, 2013 by admin

Continuing on from our preview of the first chapter of Derek Goulsbra’s new book, available here in part one, this post previews the start of chapter 2 ‘Medium Voltage Cable Accessories: A Theoretical and Practical Appraisal.

Chapter 2 – Electrical breakdown of air and solid dielectrics

In order to understand accessories and how they perform it is necessary to look at the fundamental electrical breakdown of air and solid dielectrics, which are, of necessity, mixed in dry cable accessories.

2.1: Electrical Breakdown of Air

Air at normal temperature and pressure, which means a temperature of 20 ° C and pressure of 760 mm Hg, has an intrinsic breakdown strength of 3 MV m-1 . This means that if a voltage is applied between two electrodes, which provide a uniform field, and the electrodes are spaced 10 mm apart, electrical breakdown of the air in the form of an arc will occur at 30 kV. This value is the same for a.c. (the peak value), d.c. and impulse. The electric strength is simply found by dividing the applied voltage at breakdown by the electrode separation. In the present example:

Breakdown strength E = Voltage applied / Electrode separation
= 30 kV per cm
= 3 kV per mm
= 3 MV per m

A uniform field is shown in fig.1. By definition lines of equal voltage are spaced equally across the shortest distance of the electrodes.

In practice, the intrinsic electric strength of air is of little use because conductors at high voltage are not conducive to producing a uniform field and the earth plane is often a flat sheet interspersed with bolt heads and nuts for various fixings. At the other end of the scale from a uniform field is the point-plane configuration shown in fig. 2.

Uniform Field Derek Goulsbra MV Book

Figure 1: Uniform Field

In this situation, it will be noted that the equipotential field lines are much closer together near the point electrode and spaced further apart as the earth electrode is approached. If the separation of the electrodes is again 10 mm, it will be found that the voltage required to break down the air will be as low as 10 kV, depending upon the sharpness of the point. The reason for this is that as the field lines are close together near the point, the breakdown strength of the air, i.e. 3 MV m-1 will be reached with only a few kV applied. At this point the air breaks down locally to create corona around the needle electrode. There will not be complete breakdown of the gap initially because the electric stress nearer the earth plane is very much lower. The corona produced does, however, ionise the air thus reducing its electric strength and if the voltage is increased further, total breakdown occurs at a much lower level than if the electrodes presented a uniform field.

Corona occurs in many situations without causing complete failure of the system – e.g. on overhead power lines and around insulators on these lines, especially when there is rain or fog in the atmosphere.

Whenever air is used as part of the insulation in electrical equipment, there is the possibility of corona occurring. It is not desirable for this to happen in an enclosed space and thus designers ensure that sharp profiles are eliminated and spacing is adequate to prevent corona at working voltage.

It should be borne in mind that corona in an enclosed piece of switchgear or cable box can, if the humidity is high, create various acids, which will eventually corrode the metal work of the equipment and this must be avoided. It will be shown later that this effect can also be caused by badly installed cable termination.

Filed Under: Guest Blogs

Preview: Medium Voltage Cable Accessories – A Book By Derek Goulsbra

May 29, 2013 by admin

Derek Goulsbra has been heavily involved in product development, failure analysis and engineering and jointer training for over thirty years. His new book, published by Nexans, is a detailed look at the Medium Voltage cable accessories which will be of value to jointers and engineers alike.

The book contains theoretical and practical appraisals on the workings and failure modes of a range of cabling accessories, including separable connectors, terminations, joints and associated components, as well as a practical consideration of cable preparation using present day techniques and tools prior to installing the accessory. Derek rounds the book up with a set of examples of failures which are presented with explanations of how these could have been avoided.

We have been lucky enough to get an early copy of the book and have featured the following teaser from chapters 1 and 2.

Chapter 1 – Introduction

The cables used for electrical distribution until the 1960’s almost exclusively used impregnated paper to insulate the conductors and were usually three core. A change to polymeric insulation then gradually gathered momentum and with it a change in the technology required for cable accessories, although, ironically some of the first dry terminations were developed for paper cable.

Early so-called dry type accessories for polymeric cables were usually of the pushon variety produced from elastomers and used on single core cable. The sound basic technology employed in the early days ensured that such products continue to be supplied today.

Heat shrinkable terminations were introduced in the late 1960’s and had the distinct advantage of being range taking and capable of use on both single and three core cables. Heat shrinkable joints were developed a few years later following the success of terminations and their suitability for both paper and polymeric cables resulted in a major revolution in cable accessory technology. This technology was a complete departure from the previous techniques, which required a cast iron box or lead sheath filled with oil or compound.

Cold shrink products made an appearance a little later and are now proving popular within the industry. The debate as to which system is preferable continues. It is fair to say that the heat shrinkable system is the most versatile and well known, but on single core polymeric cables in particular cold shrink systems are seen to have certain advantages. It is not the intention of the author to express a preference for any one system.

The use of screened elbows to terminate cables is now widely accepted and it will be shown later in the book that this system is theoretically superior to other systems for certain applications.

The early development of dry cable terminations concentrated on three core paper cables in the United Kingdom and single core polymeric cables in the United States of America. The accessories for paper cable were originally developed for paper belted cable rated at 11 kV using heat shrink technology; whilst for polymeric cable elastomeric push on systems were developed principally for 8, 15 and 25 kV.

As with many totally new concepts, it was shown that extensive laboratory development and testing is no substitute for field experience and many of the early terminations failed. The failures were generally not the result of poor installation, as each one was carefully monitored at this stage. The first heat shrinkable terminations developed for paper cable were pole top mounted and therefore exposed to the elements. The materials used were not themselves to blame and the formulation has changed little since that time. Several weak links in the chain were, however, present simple things such as inspection windows in cable lugs allowing water into the termination and the sealant used did not always exclude moisture. However, the major problem was the regular occurrence of breakdown between one core and the lead sheath.

Gradually, as the problems were identified, the weaknesses were eliminated and the products became reliable. At the present time dry type accessories, if installed correctly, will give satisfactory operation for the life of the system. Many terminations installed thirty years ago are still in service today.

As the practices of utilities have change and many of the jointers and engineers have retired, the need to make the installation of accessories less skill sensitive is the main driving force for the manufacturer. However, there are still some fundamental rules which should be obeyed to ensure satisfactory installation and hence trouble free service life.

A constant problem within the industry is the shortage of fully trained jointers to install the ever increasing variety of products in the market place.

The following chapters will examine how accessories work, why they can fail and good practices required ensuring trouble free service. It is hoped that there will be information of interest to engineers and jointers alike which will enable them to better understand the workings of cable accessories and hence reduce the potential for problems at a later stage.

If you found this article helpful or interesting, please share it!

Filed Under: Guest Blogs

  • « Go to Previous Page
  • Page 1
  • Interim pages omitted …
  • Page 20
  • Page 21
  • Page 22
  • Page 23
  • Page 24
  • Go to Next Page »

Primary Sidebar

Meta

  • Log in
  • Entries feed
  • Comments feed
  • WordPress.org
  • Login
  • Your quote
Useful Links
  • Request a Quote
  • Blog
  • Recruitment
  • Privacy Policy and other statements
  • Terms and Conditions
  • Cookie Policy
  • About ETS CC
  • Contact Us
  • Request a Catalogue
  • Accreditations
Contact ETS

For up to date technical data please get in touch

020 8405 6789
sales@etscablecomponents.com
E.T.S. (Portsmouth) Limited T/A ETS Cable Components
Unit 43, Barwell Business Park
Leatherhead Road, Chessington
Surrey, KT9 2NY
Get Social

Stay up to date by following us on social media

ETS Accreditations
ISO 9001 Certified Company
FORS Fleet Operator Recogintion Scheme ID: 002140
RISQS Verified
Achilles UVDB Silver Plus
ISO 14001 Certified Company
FORS Practitioner
Bronze top 35% ecovadis sustainability rating Sep 2024

Copyright 2025 ETS Cable Components. All rights reserved. Website by Tiga Creative Marketing Kent.

We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits. By clicking “Accept All”, you consent to the use of ALL the cookies. However, you may visit "Cookie Settings" to provide a controlled consent.
Accept All Cookie Settings
Manage consent

Privacy Overview

This website uses cookies to improve your experience while you navigate through the website. Out of these, the cookies that are categorized as necessary are stored on your browser as they are essential for the working of basic functionalities of the website. We also use third-party cookies that help us analyze and understand how you use this website. These cookies will be stored in your browser only with your consent. You also have the option to opt-out of these cookies. But opting out of some of these cookies may affect your browsing experience.
Necessary
Always Enabled
Necessary cookies are absolutely essential for the website to function properly. These cookies ensure basic functionalities and security features of the website, anonymously.
CookieDurationDescription
cookielawinfo-checkbox-analytics11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics".
cookielawinfo-checkbox-functional11 monthsThe cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional".
cookielawinfo-checkbox-necessary11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary".
cookielawinfo-checkbox-others11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other.
cookielawinfo-checkbox-performance11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance".
viewed_cookie_policy11 monthsThe cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data.
Functional
Functional cookies help to perform certain functionalities like sharing the content of the website on social media platforms, collect feedbacks, and other third-party features.
Performance
Performance cookies are used to understand and analyze the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Analytics
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics the number of visitors, bounce rate, traffic source, etc.
Advertisement
Advertisement cookies are used to provide visitors with relevant ads and marketing campaigns. These cookies track visitors across websites and collect information to provide customized ads.
Others
Other uncategorized cookies are those that are being analyzed and have not been classified into a category as yet.
SAVE & ACCEPT